started · updated
Lukoil Neftohim Burgas experiences emergency shutdown
An external power supply issue caused an emergency shutdown of approximately 80% of technological installations at the Lukoil Neftohim Burgas refinery. The incident followed a sharp voltage drop, nearly reaching zero, caused by a three-phase short circuit at the Kameno substation during planned maintenance.
The power disturbance consisted of three consecutive voltage fluctuations lasting 400 milliseconds, one second, and 400 milliseconds. This triggered intensive flare burning, resulting in visible black smoke and flames. The refinery explained that black smoke can occur during sudden surges of hydrocarbon gases when steam supply adjustment lags behind the gas influx.
According to the company, monitoring stations in Burgas, Kameno, and Dolno Ezero, as well as independent monitoring systems, did not detect any exceedances of controlled pollution indicators. The Electricity System Operator is expected to determine whether the short circuit was caused by human error or a technical malfunction.
Entities
Burgas · Electricity System Operator · Kameno substation · Lukoil Neftohim Burgas