Grava school complex gas safety concerns identified by TEE

A report by the Technical Chamber of Greece (TEE) has identified critical safety deficiencies in the natural gas installations at the Grava school complex. Following investigations conducted between October 17 and 19, experts found significant deviations from approved technical studies and safety regulations.

Key findings include a non-functional gas leak detection system in one boiler room and the lack of an accessible manual shut-off mechanism in another. The report also highlighted fire safety risks, noting that boilers and electrical installations coexist in the same space without fire-resistant doors. Additionally, some gas pipelines intended to be underground were found in open manholes without anti-corrosion protection, and one section was constructed from steel instead of the specified polyethylene.

While inspections did not detect an active gas leak, the source of the reported odor remains unidentified. Consequently, the Athens Municipal Council has unanimously decided to suspend the operation of the schools from October 22 to October 26, 2026. The municipality is considering installing approximately 100 air conditioning units to provide heating as an alternative to the gas system while repairs are conducted.

Entities

Athens · Athens Municipality · Giorgos Stasinous · Grava · Grava school complex · Haris Doukas · Sofia Zacharaki · Technical Chamber of Greece